documents:de4000:de4000operate [2022/11/29 17:50]
twebster [1. OVERVIEW]
documents:de4000:de4000operate [2023/05/15 13:05] (current)
twebster [8.1 Trends]
Line 2: Line 2:
 ====== - DE-4000 Operation and Configuration Manual ====== ====== - DE-4000 Operation and Configuration Manual ======
 ===== - OVERVIEW ===== ===== - OVERVIEW =====
- 
-This is a Test 
- 
- 
 This manual provides operation, configuration, and programming information that enables technicians and installers the information to configure the DE-4000 Safety Shutdown and Control System. Following in typical Altronic tradition, the DE-4000 System is highly configurable without the need for custom programming. For reference, configuration guides the technician to select setup parameters through interactive methods. Programming requires the technician to understand the problem and to write custom code in a programming language to realize a function. Altronic DE-4000 development engineers worked with in-the field application experts to gather critical information that allowed the engineers to develop this comprehensive, highly configurable system. A large number of DE-4000 System applications can be configured without the need for custom programming. However, when a custom requirement is needed, a simple, readable, script type of programming has been implemented in the DE-4000 System. This manual provides operation, configuration, and programming information that enables technicians and installers the information to configure the DE-4000 Safety Shutdown and Control System. Following in typical Altronic tradition, the DE-4000 System is highly configurable without the need for custom programming. For reference, configuration guides the technician to select setup parameters through interactive methods. Programming requires the technician to understand the problem and to write custom code in a programming language to realize a function. Altronic DE-4000 development engineers worked with in-the field application experts to gather critical information that allowed the engineers to develop this comprehensive, highly configurable system. A large number of DE-4000 System applications can be configured without the need for custom programming. However, when a custom requirement is needed, a simple, readable, script type of programming has been implemented in the DE-4000 System.
  
Line 533: Line 529:
 {{ :documents:de4000:channeltrends.png?nolink |}} {{ :documents:de4000:channeltrends.png?nolink |}}
  
 +=== - Advance Trending & Data Logging  ===
 +
 +NOTE: This feature requires an ACM4000 be installed alongside the DE4000.
 +
 +In Firmware version 3.0.0 and above the standard Trending shown in section 8.1 is replaced with a link to the Altronic Data Explorer(ADE) hosted on an ACM4000 system. Note when showing the ADE the Left side buttons are covered up so the Close button will appear where the Settings gear button usually is. Pressing this will close the ADE and show the left side buttons and the dashboard home page.
 +
 +{{ :documents:de4000:advtrend.jpg?nolink&1000 |}}
 +
 +If you don't have an ACM4000 in the system then the Advanced Trending and Data Logging can be disabled by setting a Virtual Channel in the Master Script.
 +
 +{{ :documents:de4000:advtrendenable.jpg?nolink&600 |}} 
 +
 +If an ACM4000 is added later the Advanced Trending and Data Logging can be enabled again by setting the virtual channel to "0".
 +
 +{{ :documents:de4000:advtrendDisable.jpg?nolink&600 |}}
 ===== - EVENTS ===== ===== - EVENTS =====
  
Line 1734: Line 1745:
 on the back of the HMI Display Module. on the back of the HMI Display Module.
  
-o Click the On-Screen Keyboard switch to turn the On-Screen Keyboard ON +o Click the On-Screen Keyboard switch to turn the On-Screen Keyboard ON or OFF.
-or OFF.+
  
 **• Auto-Scale —** The Auto-scale is used to stretch the DE4000 User Interface on HMIs larger then 8 inches. With this enabled it will also stretch to fit the browser window when connected through a Laptop. **• Auto-Scale —** The Auto-scale is used to stretch the DE4000 User Interface on HMIs larger then 8 inches. With this enabled it will also stretch to fit the browser window when connected through a Laptop.
Line 1747: Line 1757:
  
 **• System Info —** The System Info tab is used to display and update the current firmware/ **• System Info —** The System Info tab is used to display and update the current firmware/
-software version levels or rev levels loaded into each component of the DE-4000 system. The components are:+software version levels or rev levels loaded into each component of the DE-4000 system. If not logged in as Admin the standard System Information page will display the current firmware revisions on all boards and the Current Web Application revision loaded on the SOM. If logged in as Admin the Firmware Update page will display with the interface to allow for updating Firmware revisions on the boards as well as updating the Web Application on the SOM. See Below for instructions on updating firmware. 
 + 
 +Non-Admin:{{ :documents:de4000:sysinfo-old.jpg?nolink&800  |}} Admin:{{ :documents:de4000:bl-no-usb.jpg?nolink&805 |}}
  
 o **Web Application —** The SOM and Web App Firmware o **Web Application —** The SOM and Web App Firmware
Line 1758: Line 1770:
  
 o **Terminal Module X —** The Firmware for each Terminal Module o **Terminal Module X —** The Firmware for each Terminal Module
 +
 +=== - Firmware Updates ===
 +
 +o **Updating Firmware/Bootloader —** Updating the firmware requires a new version and a USB drive to load it onto the system. 
 +
 +{{ :documents:de4000:bl-no-usb.jpg?800 |}}
 +
 +To begin updating, download the new firmware version onto an empty flash drive and insert it into the USB port on the DE-4000. The flash drive needs 30 seconds to mount properly and display the firmware to the Controller Board. 
 +
 +{{ :documents:de4000:bl-refreshing.jpg?nolink&800 |}}
 +
 +Press System Info to enter the Firmware tab. Pressing the Refresh key in the bottom left should change the buttons to the right of each module version from “No Firmware Available” to “Firmware Available”. This change will only apply to the modules which have updated files in the USB. 
 +
 +{{ :documents:de4000:bl-ready-to-select.jpg?nolink&800 |}}
 +
 +The SOM web app, Controller, and Terminal Boards will all need to be updated separately. Pressing one of "Firmware Available" keys will display the firmware files able to be downloaded to that module from the USB in the menu below.
 +
 +{{ :documents:de4000:bl-file-selected.jpg?nolink&800 |}}
 +
 +To update after selecting a new firmware, the required conditions are: 
 +
 +o State = 0 — The DE-4000 cannot be in a “Running” state, it must be either “Fault” or “Ready to Start”
 +
 +o RPM = 0 — All of the Terminal Board RPM inputs must read 0 or be disconnected.
 +
 +o File Selected — A firmware file must be chosen from the menu
 +
 +Once all the conditions are met, the “Proceed to Update” button should light up and is now able to be selected. 
 +
 +A Confirm Selection screen will pop up upon pressing "Proceed to Update" showing the chosen firmware and module, press "Proceed" to continue.
 +
 +{{ :documents:de4000:bl-confirm-select.jpg?nolink&600 |}}
 + 
 +A Lockout/Tagout warning should appear, any connected devices should be locked out to avoid
 +accidents. Press Begin Update in the bottom right to continue. 
 +
 +{{ :documents:de4000:bl-safety-warn.jpg?nolink&800 |}}
 +
 +The HMI should display a Progress Bar screen while loading the update.
 +
 +{{ :documents:de4000:bl-progressbar.jpg?nolink&600 |}}
 +
 +When update is completed a popup message will say that the update was successfully completed. Press close on this popup. If updating a Control or Terminal Board the page will remain on the System info page. If updating the Web Application when you press the close button the web page will do a forced reload to allow the new web application to be properly loaded after the update. This will force the User Interface back to the Dashboard Home page.
 +
 +{{ :documents:de4000:bl-success.jpg?nolink&600 |}}
 +
 +The System info page will now display the updated firmware version. 
 +
 +{{ :documents:de4000:bl-newrev.jpg?nolink&600 |}}
 +