documents:mtb-etc:mtb-etcinstall [2022/10/14 12:04]
dmarkovitch
documents:mtb-etc:mtb-etcinstall [2022/10/14 12:06] (current)
dmarkovitch removed Deg2
Line 45: Line 45:
   - The power disconnect must be marked as the over-current and disconnect for the MTB-etc System.\\   - The power disconnect must be marked as the over-current and disconnect for the MTB-etc System.\\
  
 +===== - OVERVIEW =====
 ==== - Introduction ==== ==== - Introduction ====
 The MTB-etc (enhance temperature control) is a new class of instrument that extends the temperature range for K thermocouples to 1100.0°C (2012.0°F) and the J thermocouples to 860°C (1150°F).   All MTB-etc units are factory calibrated to +/- 1.0°C accuracy.  Floating point displayed values are shown in tenths of a degree.  See section 4.3 for more information how to setup the MTB-etc and the thermocouples to ensure the highest degree of accuracy.  The MTB-etc is an RS-485, MODBUS RTU slave board capable of reading 33 channels. The first 30 channels can be any combination of digital inputs (N/O or N/C), thermocouples (J or K), pressure inputs, 4-20mA inputs, or read any sensor within the range of 0-5VDC. Channels 31 and 32 can only be used for digital inputs (N/O or N/C). There is also a pickup input. Additionally, there are 8 digital outputs which are capable of sinking 60V at 500mA. Each could drive a relay, horn, or other related device. There are also two 4-20mA outputs. All the outputs are directly controlled by Modbus commands. The Modbus Terminal Board is CSA-certified for CLASS I, DIVISION 2, GROUPS C and D areas, when mounted in a suitable enclosure. The MTB-etc (enhance temperature control) is a new class of instrument that extends the temperature range for K thermocouples to 1100.0°C (2012.0°F) and the J thermocouples to 860°C (1150°F).   All MTB-etc units are factory calibrated to +/- 1.0°C accuracy.  Floating point displayed values are shown in tenths of a degree.  See section 4.3 for more information how to setup the MTB-etc and the thermocouples to ensure the highest degree of accuracy.  The MTB-etc is an RS-485, MODBUS RTU slave board capable of reading 33 channels. The first 30 channels can be any combination of digital inputs (N/O or N/C), thermocouples (J or K), pressure inputs, 4-20mA inputs, or read any sensor within the range of 0-5VDC. Channels 31 and 32 can only be used for digital inputs (N/O or N/C). There is also a pickup input. Additionally, there are 8 digital outputs which are capable of sinking 60V at 500mA. Each could drive a relay, horn, or other related device. There are also two 4-20mA outputs. All the outputs are directly controlled by Modbus commands. The Modbus Terminal Board is CSA-certified for CLASS I, DIVISION 2, GROUPS C and D areas, when mounted in a suitable enclosure.
-===== - OVERVIEW =====+
 ==== - General ==== ==== - General ====
 The DE-4000 is a Control and Safety Shutdown system specifically designed The DE-4000 is a Control and Safety Shutdown system specifically designed
Line 441: Line 442:
 Temperature transducers 691203/202-300 have a temperature measurement Temperature transducers 691203/202-300 have a temperature measurement
 range of +5 to 300°F. Temperature transducers 691212/213-450 have a temperature range of -40 to +450°F. During configuration, the 691202/203-300 range of +5 to 300°F. Temperature transducers 691212/213-450 have a temperature range of -40 to +450°F. During configuration, the 691202/203-300
-transducers are selected as Deg1 Type, the 691212/213-450 transducers are +transducers are selected as Deg1 Type, and the 691212/213-232 transducers are selected by choosing Deg3 type. The three wires from the transducers are: +5
-selected by choosing Deg2 Type, and the 691212/213-232 transducers are selected by choosing Deg3 type. The three wires from the transducers are: +5+
 volt excitation, temperature output voltage, and minus return. These wires connect directly to the Terminal Module using cable assembly P/N 693008-x. volt excitation, temperature output voltage, and minus return. These wires connect directly to the Terminal Module using cable assembly P/N 693008-x.